MAG816
8 Zone Fire Panel Expandable to 16 Zones
- Up to 16 programmable zones
- Up to 16 sounder circuits
- Active end of line monitoring and head removal
- Up to 32 fire detectors per zone
- Unlimited number of call points per zone
- Integral sound alarm button
- Repeater facility and 'Class change' facility
- Enable/disable security key
- One man walk test facility
- Volt free fire/fault change over relay
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- Alarm delay options
- CE certified to EN54 P2/4
- Requires 1 x 12V battery
- ABS casing
Technical Specifications
Inputs | |
Max. Detectors per Zone | 32 |
Thresholds for Zone Conditions | 0 - 2 mA (Fault condition) 2 - 10 mA (Normal condition) 10 - 110 mA (Fire condition) 110mA - + Short (Fault condition) |
Power | |
Mains Fail Consumption | 130mA (1 zone expander) 260mA (4 zone expanders) |
Mains Supply | 230 VAC ± 10% |
Standby Supply | 1 x 18ah 12V S.L.A. Batteries |
Power Availability | 0.7 amps |
Outputs | |
On Board Sounder Circuits (4) | 300mA @ 24V fuse resettable (PTC) |
Sounder Expander Cards (4) | 150mA @ 24V fuse resettable (PTC) |
Fault/Fire Relay | Volt free 500mA @ 24V (max load) |
Auxiliary Output | 24VDC (300mA fused) |
Environment | |
Working Temperature | 0 to 40ºC |
Storage Temperature | -20 to 60ºC |
Humidity | 0 to 93% |
Dimensions (mm) | 456 x 350 x 125mm |
Weight | 4.2 KG |