8 Zone Fire Panel Expandable to 16 Zones

  • Up to 16 programmable zones
  • Up to 16 sounder circuits
  • Active end of line monitoring and head removal
  • Up to 32 fire detectors per zone
  • Unlimited number of call points per zone
  • Integral sound alarm button
  • Repeater facility and 'Class change' facility
  • Enable/disable security key
  • One man walk test facility
  • Volt free fire/fault change over relay
  • Individual sounder circuit fault ID
  • Individual zone/sounder isolate
  • Alarm delay options
  • CE certified to EN54 P2/4
  • Requires 1 x 12V battery
  • ABS casing

Technical Specifications

Inputs
Max. Detectors per Zone32
Thresholds for Zone Conditions0 - 2 mA (Fault condition) 2 - 10 mA (Normal condition) 10 - 110 mA (Fire condition) 110mA - + Short (Fault condition)
Power
Mains Fail Consumption 130mA (1 zone expander) 260mA (4 zone expanders)
Mains Supply230 VAC ± 10%
Standby Supply1 x 18ah 12V S.L.A. Batteries
Power Availability0.7 amps
Outputs
On Board Sounder Circuits (4)300mA @ 24V fuse resettable (PTC)
Sounder Expander Cards (4)150mA @ 24V fuse resettable (PTC)
Fault/Fire RelayVolt free 500mA @ 24V (max load)
Auxiliary Output24VDC (300mA fused)
Environment
Working Temperature0 to 40ºC
Storage Temperature-20 to 60ºC
Humidity0 to 93%
Dimensions (mm)456 x 350 x 125mm
Weight4.2 KG