MAG2P

2 Zone Fire Panel

  • 2 programmable zones
  • Active end of line monitoring and head removal
  • 30 fire detectors per zone
  • Unlimited number of call points per zone
  • Integral sound alarm button
  • 'Class change' facility
  • Enable/disable security key
  • One man walk test facility
  • Volt free fire change over relay
  • Volt free fault change over relay
  • Individual sounder circuit fault ID
  • Individual zone/sounder isolate
  • CE certified to EN54 P2/4
  • Requires only 1x12v battery
  • MAG2P - ABS casing

Technical Specifications

Inputs
Max Detectors Per Zone30
Thresholds for Zone Conditions0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition)
Power
Mains Fail Consumption 50mA
Mains Supply230 VAC ± 10%
Standby Supply­­1 x 7ah 12V S.L.A. Battery
Power Availability0.7 amps
Outputs
Sounder 124V (max 300mA fused)
Sounder 224V (max 300mA fused)
Fault/Fire RelayVolt free 500mA @ 24V (max load)
Auxiliary Output24VDC (300mA fused)
Environment
Working Temperature0 to 40ºC
Storage Temperature-20 to 60ºC
Humidity0 - 95%
Dimensions MAG2P340 x 290 x 100mm
Dimensions MAG2200 x 290 x 80mm
WeightMAG2P - 2.1Kg MAG2 - 2.7Kg