MAGPRO-CZM

Conventional Zone Module with Isolator

  • Integrate conventional detectors into an addressable system
  • Max number of detectors in one zone - 32
  • Loop powered
  • Built in isolator
  • Certified to EN54-18
  • Example applications - Integrate conventional equipment i.e. beam detectors

Technical Specifications

Operating Voltage Range15-30VDC (Nom 27VDC)
Permissible Voltage Rippler3.0Vpp@27VDC
External Power Supply of the Zone15 - 32VDC
Max. Current Consumption with external power supply150uA@27VDC
Max, Current Consumption, Loop power supply5.5mA
Current Consumption with 1 LED on3mA
Max Current consumption (ALARM Mode)
When the zone is powered from +L terminal of the loop20mA
When the zone is powered from +H terminal of the loop50mA
Max number of conventional detectors in one zone32
Wire gauge for terminals0.4mm_- 2.0mm_
Operating temperature-10¡C to +60¡C
Relative Humidity Resistance(93±3)% @40¡C
ProtectionIP40
Weight320g
Material(plastic),colourPS,White
Dimensions 142x80x45mm