MAGPRO-REP01
Addressable Fire Alarm Repeater Panel

- Wall-mount design
- MAGPRO16/G requires Firmware version 4.5.2 or above
- MAGPRO96 requires firmware version 6.7.2 or above
- MAGPRO9601 requires firmware version 1.1.4 or above
- Requires 24VDC External Power Supply
- Max consumption of 0.4A (400mA)
- Each panel in network will require a MAGPRO-NIC
- Maximum of 64 panels in the network
- 1000m distance from MAGPRO-REP01 to MAGPRO Panel
- Dimensions 200 x 330 x 48mm
- Ring type network
- 10,000 event log within the repeater

Technical Specifications
Power | |
From a MAGPRO Panel | AUX / GND |
External* | 24VDC +/-4 VDC |
Consumption | 400mA |
Input | |
Communication | RS485 |
Max Length Between Panels | 1000m |
Output | |
Communication | RS485 |
Max Length Between Panels | 1000m |
Technical spec | |
Memory LOG | 10,000 events |
Network type | Ring |
MAGPRO16/G Firmware Compatibility | Ver 4.5.2 or higher |
MAGPRO96 Firmware Compatibility | Ver 6.7.2 or higher |
MAGPRO9601 Firmware Compatibility | Ver 1.1.4 or higher |
Max number of panels | 64 |
Connection to MAGRO Panel | Via MAGPRO-NIC |
Environment | |
Working Temperature | -5°C to +40°C |
Humidity | 95% |
Weight | 500g |
Dimension | 200 x 330 x 48mm |