MAGPRO9601
Addressable 96 Zone Fire Alarm Panel
- 96 Zones
- Maximum 250 devices per loop
- Memory Log: 10,000 events
- Networkable up to 32 Panels
- 800 x 480 pixel touch screen display
- Free programming software (On completion of training - UK)
- Micro USB port for PC connection
- Loop & battery calculator software included
- Certified to EN54–2/4
Technical Specifications
Inputs | |
Loops | 1 expandable to 4 |
Devices Per Loop | Up to 250 |
Protocol | MAGPRO |
Power | |
Current Consumption | 2.7A |
Mains Supply | AC230V +10/-15% |
Backup | 1x12V 18Ah |
Outputs | |
1 Sounder | 24v DC @ 500mA |
4 Programmable (non-monitored) Relays | 24v DC @ 15A |
4 Monitored Outputs | SND (Conventional Sounder Circuit): 24V DC @ 0.5A Fire R (Fire Alarm): 24V DC @ 0.1A Fire P (Fire Protection): 24V DC @ 0.1A Fault R (Fault): 24V DC @ 0.1A |
1 Auxillary Output | 24v DC @ 300mA |
Environment | |
Working Temperature | -5°C to +40°C |
Storage | -10°C to 60°C |
Humidity | <95% |
Dimensions | 430 x 350 x 120mm |