16621

Standard Panel 24 hr Timer (with battery)

  • Voltage free 16A changeover contact
  • Suitable for Surface, Panel or Din rail mounting
  • 200 hour battery reserve (16621 only)
  • Programming by 10 min captive segments
  • Manual override with automatic return to program
  • Contact status display
  • Optional accessory 95583 panel kit is available

Technical Specifications

Power Supply 230V AC, 50/60Hz
Programming24 hour
DisplayAnalogue
MountingOptional
Current Rating16A
Switching Capacity Resistive load 16A 250V Voltage free inductive load (cos = 0.6) 3A 250V Incandescent lamp 1000W 250V Squirrel-cage motor 350W 250V
Reserve200 hour
Switching Operations144 per day
Temperature Range-10°C to +50°C
Storage Temperature-20°C to +60°C
Connection by cage terminals, section of conductors 1 to 6 mm2
Insulation class2
ProtectionIP20
Dimensions72 x 72 x 49 mm
Complies withBS EN 60730